Protocol/compatibility: Compatible with C-TEC's CFP, FP, MFP and EP203 conventional fire alarm panels and virtually all other makes (testing on thir...
  • Protocol/compatibility: Compatible with C-TEC's CFP, FP, MFP and EP203 conventional fire alarm panels and virtually all other makes (testing on third-party panels is recommended before use)
  • Application/operation: Designed to be ceiling mounted – either stand-alone with a red or white cap or as part of a stacked Voice Sounder/VAD/Detector Base combination
  • VAD category & coverage: O-R-3-2.5-17 Rectangular coverage – ideal for corridor spaces
  • Flash rate & colour: 0.5Hz; 1Hz or OFF / White
  • Supply/operating voltage: 18 to 30V DC
  • Alarm current: At 30Vdc: 17mA (0.5Hz) or 24mA (1Hz); At 18Vdc: 18.5mA (0.5Hz) or 30mA (1Hz)
  • Product dimensions (mm): 122 x 46 (not including optional detector and base)
  • IP Rating: IP21C (Type A)
  • Weight: 170g
  • Operating conditions/temperature: -10 to 55ºC
  • Notes: Choose from 2 evacuation voice messages and 4 evacuation tones. Note all of these have an associated alert tone/message, the activation of which requires additional wiring and control functionality

In stock

SKU BF455C/CC/W